No products in the cart.
- Anti-Trip Technology for complete trip free Loop testing on all RCDs rated 30mA and above.
- Dual Display allows simultaneous measurements like Loop & PFC/PSC.
- Two wire connection for Loop L-L, L-N and PSC testing is possible.
- Phase rotation, Voltage and Frequency measurements.
- Lock-down test button for ‘hands free’ testing with auto-start operation.
Specification | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Loop Impedance | |||||||||||||||||
Function | L-PE ATT OFF | L-PE ATT ON | L-N / L-L | ||||||||||||||
Rated Voltage | 230V (50/60Hz) | L-N: 230V (50/60Hz) L-L: 400V (50/60Hz) | |||||||||||||||
Operating Voltage | 100 - 280V (45 - 65Hz) | 100 - 500V (45 - 65Hz) | |||||||||||||||
Range (Auto-Ranging) | 20/200/2000Ω | 20/200/2000Ω (L-N<20Ω) | 20Ω | ||||||||||||||
Nominal Test Current at 0Ω External Loop: Magnitude/Duration at 230V | 20Ω: 6A/40ms 200Ω: 2A/20ms 2000Ω: 15mA/500ms | L-N: 6A/60ms N-PE: 10mA/approx.5s | 20Ω: 6A/20ms | ||||||||||||||
Accuracy | ±3%rdg±4dgt (*1) | ±3%rdg±6dgt (*1) | L-N: ±3%rdg±4dgt L-L: ±3%rdg±8dgt | ||||||||||||||
PFC (L-PE) / PSC (L-N / L-L) (*2) | |||||||||||||||||
Function | PFC | PFC (ATT) | PSC | ||||||||||||||
Rated Voltage | 230V (50/60Hz) | L-N: 230V (50/60Hz) L-L: 400V (50/60Hz) | |||||||||||||||
Operating Voltage | 100 - 280V (45 - 65Hz) | 100 - 500V (45 - 65Hz) | |||||||||||||||
Range (Auto-Ranging) | 2000A/20kA | 2000A/20kA (L-N<20Ω) | 2000A/20kA | ||||||||||||||
Nominal Test Current at 0Ω External Loop: Magnitude/Duration at 230V | 20Ω: 6A/40ms 200Ω: 2A/20ms 2000Ω: 15mA/500ms | L-N: 6A/60ms N-PE: 10mA/approx.5s | 20Ω: 6A/20ms | ||||||||||||||
Phase Rotation | |||||||||||||||||
Operating Voltage | 50 - 500V, 45 - 65Hz | ||||||||||||||||
Remarks | Correct phase sequence: displayed "1.2.3" and mark Reversed phase sequence: displayed "3.2.1" and mark | ||||||||||||||||
Volts | |||||||||||||||||
Function | Volts | Frequency | |||||||||||||||
Measuring range | 0 - 500V | 45 - 65Hz | |||||||||||||||
Accuracy | ±2%rdg±4dgt | ±0.5%rdg±2dgt | |||||||||||||||
General | |||||||||||||||||
Applicable standards | IEC 61010-1 CAT III 300V (500V L to L), IEC 61010-031, IEC 61557-1, 3, 7, 10, IEC 60529 (IP54), IEC 61326 (EMC) | ||||||||||||||||
Power source | 1.5V AA batteries × 6 *Use of alkaline batteries (LR6) is recommended. | ||||||||||||||||
Dimensions | 84 (L) × 184 (W) × 133 (D) mm | ||||||||||||||||
Weight | 860g (including batteries) | ||||||||||||||||
Accessories included | Main cord (*3) Distribution board test lead (*4) 9155 (Shoulder strap) 9156 (Soft case) LR6 (Battery) × 6, Instruction manual |