Kyoritsu 4118A

 

 

Note : Harga dapat berubah sewaktu-waktuAuthorized Distributor
  • Custom microprocessor controlled for highest accuracy and reliability.
  • 3 LEDs for checking correct wiring status.
  • 15mA LOOP measurement:
    LOOP impedance 2000Ω range measurement is carried out with low test current (15mA).
    The current will not cause tripping out involved RCD even the one with the lowest nominal differential current (30mA).
  • Direct reading of Prospective Short Circuit Current (PSC).
  • Safe voltage measurement function.
  • Large custom digital display readout on all models.
  • Measure low loop resistances(resolution of 0.01Ω)
  • Automatic lock-out if test resister overheats.
  • Large custom digital display readout .
  • Visual indication of reversed phase and neutral wiring at socket.
  • Designed to IP54 Rating
  • Complies with IEC 6155
Specification
Loop Impedance Ranges 20/200/2000Ω
Loop Impedance Accuracy |±2%rdg±4dgt
AC Test Current 20Ω 25A 200Ω 2.3A 2000Ω 15mA
AC Test Period 20Ω (20ms) 200Ω (40ms) 2000Ω (280ms)
PSC Ranges 200A (2.3A 40ms) 2000A (25A 20ms) 20kA (25A 20ms)
PSC Ranges Accuracy Consider accuracy of Loop impedance
Voltage 110V-260V ±2%rdg±4dgt
Operating Voltage 230V+10% -15% (195V - 253V) 50Hz
Safety Standard IEC 61010-1 CAT III 300V IEC 61557-1,-3 IEC 61010-2-031 Pollution Degree 2
IP Rating IEC 60529-IP54
Dimensions 185(L) × 167(W) × 89(D)mm
Weight 750g approx.
Accessories Molded plug test leads 7121B (Simplified measurement probe) Pouch for test leads Shoulder Strap Instruction Manual